TOLL

What software pays for, recorded every six hours.

Snapshot
2026-10-13 14:08 UTC
Sweep
daily-2026-10-21 · finished 2026-10-21 22:33 UTC
Listed
32,435

hvac duct size derived

x402-agent-api.onrender.comInferencederived

POST https://x402-agent-api.onrender.com/api/v1/hvac-duct-size

passlisted in Coinbase#18 by calls of 30 on this host

0.002 USDC

per call, as the listing declares it on eip155:8453

Compare with anotherEvery figure as JSONCite this page

the price, as of 2026-10-13 14:08 UTC · method · pinnable

Validation state
pass
as of 2026-10-21 08:48 UTC · method · pinnable · sweep daily-2026-10-21
Uptime, 7 / 30 / 90 days
100% / 100% / 100%
as of 2026-10-21 08:48 UTC · method · pinnable · 7 of 7 in 7d, 16 of 16 in 30d, 16 of 16 in 90d
Calls, trailing 30 days
2
as of 2026-10-13 14:08 UTC · method · pinnable
Unique payers, trailing 30 days
2
as of 2026-10-13 14:08 UTC · method · pinnable
Last called
2026-10-07 14:45 UTC
as of 2026-10-13 14:08 UTC · method · pinnable
First observed by TOLLderived
2026-10-07
as of 2026-10-07 05:57 UTC · method · pinnable · observation began 10 September 2026; listings that predate it show that date
Pricederived
0.002 USDC
as of 2026-10-13 14:08 UTC · method · pinnable · on eip155:8453
Networks
1
as of 2026-10-13 14:08 UTC · method · pinnable

Counters

19 observations, 2 of them a change, fewer than the 3 a trace needs

How big is this endpoint among the ones like it?

1 call100,000this endpoint
Calls counted in the trailing thirty days across the 8,525 endpoints in Inference that carry counters, binned on a logarithmic scale because the range runs over five orders of magnitude. The marked bin is this endpoint, at 2: 1,355 in the category are counted higher and 7,169 lower.

No trace is drawn of this endpoint’s own volume. Its counters have changed 2 times across 19 observations, and 3 changes are the fewest this site will draw a trace through, because two points and a guess are not a series. Every observation is in the JSON.

In words

Of x402-agent-api.onrender.com's 30 listings, hvac duct size ranks tied 18th by calls with 6 others.

Callers of hvac duct size supply a json body with the fields airflow and friction_rate.

A response from hvac duct size, as declared, includes notes, round, steps, units, checks, airflow and 2 others.

hvac duct size drew 2 calls from 2 unique payers in the trailing 30 days, every call from a different payer.

hvac duct size was last called 6 days before the snapshot.

A call to hvac duct size costs 0.002 USDC on Base, as declared.

hvac duct size takes 2% of the calls counted across x402-agent-api.onrender.com.

TOLL files hvac duct size under inference: a POST endpoint on x402-agent-api.onrender.com, listed in the Coinbase registry.

hvac duct size answered the sweep of 2026-10-21 with a valid 402, as at every sweep since 2026-10-07.

Closest in price to hvac duct size within inference: chat completions at api.ai-open-models.com and rerank at agent402.tools.

hvac duct size is among the cheapest in inference; 4% of comparable listings ask less.

The wallet paid by hvac duct size is the payee of 30 endpoints on one host.

The seller's tags on hvac duct size are hvac, duct-sizing, engineering and mechanical-engineering.

197 other listings in inference declare exactly the same price.

Payment options as declared

the payment options, as of 2026-10-13 14:08 UTC · method · pinnable

Every payment option declared on this listing
registrynetworkassetamountschemepay to
Coinbaseeip155:8453USDC0.002 USDCexact0x684723…0043aC

Preflight checks at the last sweep

the checks, as of 2026-10-21 08:48 UTC · method · pinnableendpoint answered HTTP 402

No named check failed.

Validation history, 90 days

Every sweep that observed this endpoint, newest first.

Validation observations over the last 90 days
observed, UTCstatefailed checkssweep
2026-10-21 08:48 UTCpass0daily-2026-10-21
2026-10-20 08:59 UTCpass0daily-2026-10-20
2026-10-19 06:35 UTCpass0daily-2026-10-19
2026-10-18 08:45 UTCpass0daily-2026-10-18
2026-10-17 18:47 UTCpass0daily-2026-10-17
2026-10-16 04:59 UTCpass0daily-2026-10-16
2026-10-15 06:35 UTCpass0daily-2026-10-15
2026-10-14 04:55 UTCpass0daily-2026-10-14
2026-10-13 09:25 UTCpass0daily-2026-10-13
2026-10-12 06:50 UTCpass0daily-2026-10-12
2026-10-11 05:12 UTCpass0daily-2026-10-11
2026-10-10 13:26 UTCpass0daily-2026-10-10
2026-10-09 05:24 UTCpass0daily-2026-10-09
2026-10-08 07:05 UTCpass0daily-2026-10-08
2026-10-07 06:20 UTCpass0daily-2026-10-07
2026-10-07 06:01 UTCpass0new-after-daily-2026-10-07

Registry presence

Presence in a registry, not liveness of the service (method). Newest first.

  1. listed in Coinbase

Declared input and output, as listed

From the registry record, not validated by TOLL.the declared schema, as of 2026-10-07 14:45 UTC · method · live

The input and output block
{
  "input": {
    "body": {
      "airflow": 1000,
      "friction_rate": 0.08
    },
    "type": "http",
    "method": "POST",
    "bodyType": "json"
  },
  "output": {
    "type": "json",
    "example": {
      "notes": [
        "The rectangular size has the same friction loss and airflow as the round duct (ASHRAE equivalent diameter); its velocity is lower because its area is larger.",
        "Galvanized steel (ε = 0.0003 ft) and standard air (0.075 lb/ft³, 70 °F, sea level). Fittings and transitions are not included.",
        "For design guidance; the engineer of record is responsible for final selections."
      ],
      "round": {
        "area": 1.1112,
        "diameter": 14.27,
        "velocity": 900,
        "friction_rate": 0.08,
        "standard_sizes": [
          {
            "best_fit": true,
            "diameter": 14,
            "velocity": 935,
            "friction_rate": 0.088
          },
          {
            "best_fit": false,
            "diameter": 16,
            "velocity": 716,
            "friction_rate": 0.0457
          }
        ]
      },
      "steps": [
        {
          "step": "Round diameter at the friction rate (equal friction)",
          "reference": "ASHRAE Handbook—Fundamentals (2021), Ch. 21 Duct Design",
          "calculation": "Iterated the diameter (bisection) until the Darcy-Weisbach friction loss at 1,000 CFM equals 0.0800 in. w.g./100 ft → D = 14.27 in"
        },
        {
          "step": "Square equivalent",
          "reference": "ASHRAE Handbook—Fundamentals (2021), Ch. 21 Duct Design (Huebscher equivalent diameter)",
          "calculation": "For W = H = S: De = 1.30·S^1.25 / (2S)^0.25 = 1.09317·S → S = 14.27 / 1.09317 = 13.06 in"
        },
        {
          "step": "Round duct: Reynolds number",
          "reference": null,
          "calculation": "Re = D·V / ν = 1.1895 ft × 14.998 ft/s / 1.56×10⁻⁴ ft²/s = 114,361"
        }
      ],
      "units": "IP",
      "checks": {
        "friction": "Typical design range (0.04-0.15 in. w.g./100 ft; about 0.3-1.2 Pa/m).",
        "velocity": "Normal design range (400-2,500 FPM; about 2-12.7 m/s).",
        "aspect_ratio": null
      },
      "airflow": 1000,
      "velocity": 900,
      "next_calls": [
        {
          "why": "What cooling load does 1000 CFM carry from 80/67 to 55/54 °F?",
          "tool": "hvac_coil_load",
          "price": "$0.002",
          "arguments": {
            "units": "IP",
            "airflow": 1000,
            "leaving": {
              "dry_bulb": 55,
              "wet_bulb": 54
            },
            "entering": {
              "dry_bulb": 80,
              "wet_bulb": 67
            }
          }
        }
      ],
      "references": [
        "ASHRAE Handbook—Fundamentals (2021), Ch. 21 Duct Design",
        "SMACNA HVAC Duct Design Manual (standard sizes, aspect ratio guidance)"
      ],
      "solved_for": "size",
      "inputs_used": {
        "airflow": 1000,
        "friction_rate": 0.08
      },
      "rectangular": {
        "area": 1.184,
        "basis": "equal_friction",
        "width": 13.06,
        "height": 13.06,
        "velocity": 845,
        "aspect_ratio": 1,
        "friction_rate": 0.08,
        "standard_sizes": [
          {
            "width": 14,
            "height": 14,
            "best_fit": false,
            "velocity": 735,
            "aspect_ratio": 1,
            "friction_rate": 0.0568,
            "equivalent_diameter": 15.3
          },
          {
            "width": 16,
            "height": 12,
            "best_fit": false,
            "velocity": 750,
            "aspect_ratio": 1.33,
            "friction_rate": 0.0605,
            "equivalent_diameter": 15.11
          }
        ],
        "equivalent_diameter": 14.27
      },
      "unit_labels": {
        "area": "ft²",
        "load": "MBH (1,000 BTU/h)",
        "grains": "gr / lb dry air",
        "length": "in",
        "airflow": "CFM",
        "density": "lb / ft³",
        "enthalpy": "BTU / lb dry air",
        "pressure": "psia",
        "velocity": "FPM",
        "elevation": "ft",
        "condensate": "gal / h",
        "temperature": "°F",
        "friction_rate": "in. w.g. / 100 ft",
        "humidity_ratio": "lb water / lb dry air",
        "specific_volume": "ft³ / lb dry air",
        "relative_humidity": "%",
        "velocity_pressure": "in. w.g."
      },
      "friction_rate": 0.08,
      "primary_shape": "round",
      "friction_factor": 0.01885,
      "reynolds_number": 114361,
      "velocity_pressure": 0.0505
    }
  }
}
Cite this page

The pinned URL below renders this page from the snapshot of 2026-10-13 14:08 UTC and does not change; the live page does, every six hours. Data reuse is under CC BY 4.0 (terms).

Plain text

TOLL, "hvac duct size on x402-agent-api.onrender.com", snapshot of 2026-10-13 14:08 UTC. https://tollindex.com/e/x402-agent-api-onrender-com-api-v1-hvac-duct-size-2da5b0/at/2026-10-13T14-08Z. Accessed [access date].

BibTeX

@misc{toll-e-x402-agent-api-onrender-com-api-v1-hvac-duct-size-2da5b0-2026-10-13T14-08Z,
  author = {TOLL},
  title = {hvac duct size on x402-agent-api.onrender.com},
  howpublished = {\url{https://tollindex.com/e/x402-agent-api-onrender-com-api-v1-hvac-duct-size-2da5b0/at/2026-10-13T14-08Z}},
  year = {2026},
  month = {10},
  note = {Pinned view of the snapshot of 2026-10-13 14:08 UTC. Accessed [access date].}
}

Reports and replies about this endpoint

None yet. Anything submitted through the form below is published here with its outcome.

Report an error about hvac duct size, or reply as the named seller

No account, no token. Published unedited with its outcome, upheld or not. Do not include personal data.

Kind

Published as typed. Optional.

10 to 4,000 characters.

Verify with the payee wallet (optional, EVM)

Sign this message with the wallet named on the page and paste the signature; it is checked, stored, never published. TOLL reply about endpoint 2da5b09dbaa1ddfd95eb84c6f57d23f97d5025a9bd735450e6a314fb1535f863 from wallet 0x6847231bD28E16A0A57c59793f6B8BD8CC0043aC

The 0x address named as payee on this page, 42 characters.

The hex signature of the message above, starting 0x.